Skip to main content

Hotspot

checks the surface temperature of the processed material.

REMBE® HOTSPOT
Made in Germany
Particularly plants that are at risk of explosive dust must frequently be provided with explosion protection measures, as ignition sources are often unavoidable. In addition to electrostatic phenomena and mechanically generated functions, the most frequent ignition sources particularly include glowing embers, open flames and hot surfaces. Alongside grounding monitoring systems and spark extinguishing systems, the Hotspot detector series make an enormous contribution to increasing explosion safety. The Hotspot series have been developed for the early identification of combustion reactions and thermal events, which can ultimately be ignition sources for explosions.
Application
The Hotspot thermographic detector is specifically tailored for the early detection of hot surfaces and fire in dust-handling equipment, such as silos, dryers (excluding spray dryers), mills, conveyors or dust collectors.
REMBE HOTSPOT with Accessoires

Cable

Junction box

Advantages
  • Explosion prevention with early detection of smouldering and developing fires.
  • Highest moisture and dust resistance with unique diffusion filter technology.
  • Comprehensive explosion safety concepts through the integration of the detectors into the REMBE® EXKOP® Express control system.
Funktionsweise GSME
Mechanism
Hotspots are freely parametrisable infrared camera systems in the form of detectors with integrated signal evaluation. In addition to process monitoring, they are also particularly suitable for the detection of overheating plant components and glowing embers.
Technical data
Mechanical properties
Housing
Coated die-cast aluminium (corrosion-resistant)
Weight
0.6 kg (without power cable)
Protection class
IP 64
Explosion safety
Ex ta IIIC 105 °C Da (approval in accordance with ATEX and IECEx)
Thermal properties
Relative humidity
0 to 99 % relative humidity (non-condensing)
Temperature
-20 to +50 °C
Detection properties
Sensor resolution
32 x 31 Pixel
Viewing angle
53° x 52°
Reaction time
1 s
Time resolution
0.1 s or 1 s (depending on the configuration)
 
Electrical properties
Voltage supply
20 to 40 V DC
Power consumption
10 VA
Internal fuse protection
750 mA
M-Bus Max. line length
≈ 2 km
M-Bus Max. line capacity
≈ 200 nF
M-Bus Baud rate
4800 baud
Limit value contact alarm relay
680 Ω , 20 mA max. (Alarm closer)
Limit value contact fault relay
0 Ω, 40 V or 20 mA max. (Fault opener)
Sealing air
Purity classes
Dust ≥ 2 — Water content ≥ 3 — Oil content ≥ 2
Airflow rate
200 to 300 l/h (poss. test necessary)
Applications + Industries
  • aerospace
  • animal feed productions
  • autoclaves
  • condensers
  • desalination plants
  • dual-fuel engines
  • elevators
  • flare stacks
  • food
  • LNG
  • mills and grinding plants
  • reactors
  • reverse osmosis systems
  • separators
  • silo
  • water injection pumps

Certifications

ATEX

ATEX

IECEx

IECEx

In contrast to conventional fire detection systems, the selection and positioning of special fire detectors is a particular challenge for industrial environments. The arrangement and alignment of the detectors should therefore be exclusively specified by specialist planners.

Click and drag image to view.

Scan the QR code with your iOS camera* to see an AR preview of the product.
Hotspot AR Viewer Ru
The dimensions shown may differ from those of the actual product.
* Requires iOS 13, iPadOS 13, ARCore 1.9 or higher.
Your contact person
I will be happy to advise you about the most suitable Protection systems for your plant. Individually, in detail and taking all relevant parameters into ­account.
Alexander Kemmling | Sales Executive Explosion Prevention
Consulting. Engineering. Products. Service.
REMBE® GmbH Safety+Control